80 MVA Transformer
80 MVA Transformer
80 MVA Transformer
80 MVA Transformer
80 MVA Transformer
80 MVA Transformer
FeaturedPopular

80 MVA Transformer, Off load Tap Changing Type, Onan Cooling, Rated voltage 66±2×2.5% / 11.5 kV50 HZ, Year 2011, Test Report 2016, Manufacture Chint. Very good condition,

RATING

 

80 MVA
RATED VOLTAGE ( 50Hz )

 

66±2×2.5%  /  11.5 kV

 

NO OF PHASESThree Phase
TYPE OF COOLINGONAN/ONAF
YEAR OF MANUFACTURE2011
TAP CHANGER TYPE

 

OFFLOAD

1.2 GENERAL CHECKS:

DescriptionRemarks
Primary Voltage selector switchOK
Earthing connection satisfactoryOK
All Protection Covers fittedOK
All rating, diagram, ID plates fitted & satisfactoryOK
Tightness of all fastenersOK

80 MVA Transformer

  1. INSULATION RESISTANCE MEASUREMENT:
         DescriptionR 60 seconds (GΩ)Remarks
HV to LV + Earth (5000V)64.8 GΩok
HV to LV  (5000V)42.1 GΩok
LV to HV + Earth (5000V)72.5 GΩok
Core to Earth ( 500 V )9.87 GΩok
Core Clamp to Earth ( 500 V )6.90 GΩok

3.1 TURNS RATIO TEST:  A Phase

HV (  0 – A  )                   LV (  a – c  )

 

HV

 

LV

 

Applied  Voltage on HV

 

 

 

Measured Voltage on LV

Measured Turns Ratio 

Magnetizing Current mA

 

Tap

 

 

Voltage

( V )

 

Tap

 

 

Voltage

( V )

169300 

 

 

/

 

 

 

11500

499.90144.363.463024.90
267650499.88147.633.386025.84
366000499.87151.653.296227.09
464300499.80155.903.206527.24
567200499.90159.733.129528.51

3.2 TURNS RATIO TEST:   B Phase

HV (  0 – B  )                   LV (  b – a  )

 

HV

 

LV

 

Applied  Voltage on HV

 

 

 

Measured Voltage on LV

Measured Turns Ratio 

Magnetizing Current mA

 

Tap

 

 

Voltage

( V )

 

Tap

 

 

Voltage

( V )

169300 

 

 

/

 

 

 

11500

499.83143.643.480313.91
267650499.89155.063.313614.48
366000499.89150.863.223615.21
464300499.88146.883.203315.44
567200499.84158.843.146915.99

3.3  TURNS RATIO TEST:  C Phase

HV (  0 – C  )                   LV (  b – c  )

 

HV

 

LV

 

Applied  Voltage on HV

 

 

 

Measured Voltage on LV

Measured Turns Ratio 

Magnetizing Current mA

 

Tap

 

 

Voltage

( V )

 

Tap

 

 

Voltage

( V )

169300 

 

 

/

 

 

 

11500

499.89143.743.477817.23
267650499.88146.983.400917.69
366000499.88150.973.311218.54
464300499.89155.183.221419.49
567200499.89158.973.144520.37

4.1  WINDING RESISTANCE TEST:  HV SIDE

HV Windings 0 -A                                              Ambient Temp:  45ᵒC

 

HV

 

WINDING RESISTANCE

m

 

 

DC  I

A

 

 

DC  mV

 

Tap

 

 

Voltage

( V )

16930061.176.8167417.01
26765060.666.8160413.45
36600056.156.8195382.89
46430056.296.8143383.56
56720056.036.6826382.45

 

4.2  WINDING RESISTANCE TEST:  HV SIDE

HV Windings   0 – B                                     Ambient Temp:  45ᵒC

 

HV

 

WINDING RESISTANCE

m

 

 

DC  I

A

 

 

DC  V

 

Tap

 

 

Voltage

( V )

16930058.996.8122400.21
26765058.736.8145401.82
36600057.446.8188391.69
46430054.736.8134372.91
56720054.266.8186369.99

4.3  WINDING RESISTANCE TEST:  HV SIDE

HV Windings   0 – C                                           Ambient Temp:  45ᵒC

 

HV

 

WINDING RESISTANCE

m

 

 

DC  I

A

 

 

DC  V

 

Tap

 

 

Voltage

( V )

16930066.996.8122456.34
26765064.766.8086440.95
36600064.636.8042439.73
46430063.196.8096430.27
56720062.816.8141427.96

 

5.1  WINDING RESISTANCE TEST:   LV SIDE

LV Windings   a – b                                                                                Ambient Temp:  45ᵒC

 

LV

 

WINDING RESISTANCE

m

 

 

DC  I

A

 

 

DC  V

 

Tap

 

 

Voltage

( V )

 

a  –  b

 

11500

3.404 

6.8426

 

23.289

80 MVA Transformer

5.1  WINDING RESISTANCE TEST:   LV SIDE

LV Windings   b – c                                                                                 Ambient Temp:  45ᵒC

 

LV

 

WINDING RESISTANCE

m

 

 

DC  I

A

 

 

DC  V

 

Tap

 

 

Voltage

( V )

 

b  –  c

 

11500

3.504 

6.8566

 

24.022

5.1  WINDING RESISTANCE TEST:   LV SIDE

LV Windings   c  –  a                                                                              Ambient Temp:  45ᵒC

 

LV

 

WINDING RESISTANCE

m

 

 

DC  I

A

 

 

DC  V

 

Tap

 

 

Voltage

( V )

 

c  –  a

 

11500

3.502 

6.8606

 

25.305

About Transformers

80 MVA Transformer

Overview

  • Category : Transformer
  • Item Number : P80
  • Offer Type : For Sale
  • Quantity : 1
  • Manufacture : Ch
  • Condition : Used
  • Voltage : 66±2×2.5% / 11.5 kV
  • Frequency : 50 HZ
  • Phase : 3
  • Cooling : Onana
  • Year of Manufacture : 2011