The MWM TCG 2020 Generators. 1400 KW MWM TCG 2020 V16K (K Series is Optimized for robustness and low CAPEX) Gas Generators in Sound Attenuated Enclosures, Natural Gas Fuel, 1400 KW Continuous, 1800 rpm, 480 Volt, 60 HZ. Control Panel, Breakers, Synchronization Panels, Exhaust, Cooling System, Gas System and etc. Large quantity of parts available. Twenty-Nine (29) Complete Packages available. Well maintained and serviced according to MWM Service Schedule. Power Modules can be transported to your location and set up immediately to generator power. The TCG2020K engines runs on all types of fuel: natural gas, biogas, landfill gas, sewage gas, mine gas and more.
MWM TCG 2020 Generators Specifications
Engine
- Manufacture: MWM
- Model: TCG 2020 V16K (K Series is Optimized for robustness and low CAPEX
- Fuel: Natural Gas
- Electrical Output: 1400 KW
- RPM: 1800 rpm
- Rating: Continuous Duty
Alternator
- Manufacture: Stamford
- Frame: HC1734G2 CG
- KVA.BR:1800 KVA
- RPM: 1800 rpm
- Frequency: 60 HZ
- Voltage: 480 volt
- Phase: 3
- Amps. Br: 2259
- P.F.:0.08
- Rating: Continuous Duty
- Ex.Amps:3.7
- Ambient Temperature C: 40 C
- Enclosure: IP23
- Insulation Class: H
- BR Rating to Temp R: H
- Stator WDG: 12
- Stator Con: STAR
- AVR: MX321
Information supplied from the MWM website
Generators Description – MWM Gas Engine TCG 2020 /TCG 2020 K
Runs on all gas types: natural gas, biogas, landfill gas, sewage gas, mine gas, etc.
Low operating costs
The TCG 2020 K was especially adapted to non-ISO conditions such as high altitudes or high intake air temperatures in the field of natural gas
Save Money with the TCG 2020 – High Profitability Thanks to High Efficiency
- With Improvements of the intake duct and spark plug provide higher efficiency compared to predecessor model
- Miller valve control times increase genset efficiency
TCG 2020 K – Optimized for Isolated Operation and Non-ISO Conditions
- Load response in only seven steps
- Fast and reliable supply in the event of grid failures or in isolated operation
- Special 1,000 kWelvariant available for high altitude setup and different intake air temperatures
Higher Efficiency and Lower Pollutant Emissions
- Smaller dead spaces in combustion chamber ensure more complete combustion
- Reduced fuel consumption and CO and HC emissions
- This enables gas savings of up to 15 percent a year and increases the profitability of the plant
Higher Efficiency and Long Maintenance Intervals
- Effective crankcase ventilation increases efficiency by utilizing the returned combustible blow-by gas
- Optimized blow-by return and improved separation of the gas phase and liquid phase enable longer maintenance intervals for the turbocharger thanks to the clean intake air
TCG2020 Generator K Editions: Maximum Output at Low Costs
- Improved output capacity of TCG 2020 K under non-ISO conditions and excellent load response through optimum turbocharger design with broad performance map
- New turbocharger TCR 16 for TCG 2020 with water-cooled bearing housing eliminates need for separate maintenance stages for the turbocharger
High Reliability – MWM Gas Engine TCG 2020 /TCG 2020 K
Few Interruptions Due to Long Maintenance Intervals
- No more than two interruptions a year due to scheduled maintenance
- Longest interval until major overhaul compared to competitors
- Use of Xchange components enables time savings of up to 75 percent during the major overhaul, resulting in reduced costs
High Reliability through Mature Drive Technology in 60 Hz Range
- Engine can be operated with an optimum speed of 1500 RPM.
- Lower speed ensures stable and complete combustion, resulting in lower CO emissions and less component wear and tear
Natural gas applications, NOx ≤ 500 mg/Nm3 *
CG 2020 V16 K K = Optimized for robustness and low CAPEX | TCG 2020 V16 R = Optimized for high total efficiency | ||||
Engine type | 50 Hz | 60 Hz | 50 Hz | 60 Hz | |
Electrical output | kW | 1500 | 1500 | 1560 | 1560 |
Thermal output ± 8% | kW | 1675 | 1686 | 1576 | 1589 |
Electrical efficiency | % | 40.9 | 40.6 | 43.3 | 43.0 |
Thermal efficiency | % | 45.7 | 45.7 | 43.8 | 43.8 |
Total efficiency | % | 86.6 | 86.3 | 87.1 | 86.8 |
Power to heat ratio ** | 0.89 | 0.89 | 0.99 | 0.98 |
Optimized for operation with biogases
TCG 2020 V16 X = Optimized for operation with biogases | TCG 2020 V20 X = Optimized for operation with biogases | ||||
Engine type | 50 Hz | 60 Hz | 50 Hz | 60 Hz | |
Electrical output | kW | 1560 | 1560 | 2000 | 2000 |
Thermal output ± 8% | kW | 1566 | 1580 | 2010 | 2024 |
Electrical efficiency | % | 42.7 | 42.3 | 43.0 | 42.7 |
Thermal efficiency | % | 42.9 | 42.8 | 43.2 | 43.2 |
Total efficiency | % | 85.6 | 85.1 | 86.2 | 85.9 |
Power to heat ratio ** | 1.00 | 0.99 | 1.00 | 0.99 |
Specifications and Service Intervals –
MWM Gas Engine TCG 2020 / TCG 2020 K
TCG 2020 V16 K K = Optimized for robustness and low CAPEX | TCG 2020 V16 R = Optimized for high total efficiency X = Optimized for operation with biogases | ||||
Engine type | 50 Hz | 60 Hz | 50 Hz | 60 Hz | |
Length | mm | 5430 | 6640 | 5430 | 6640 |
Width | mm | 1810 | 1790 | 1810 | 1790 |
Height | mm | 2210 | 2210 | 2210 | 2210 |
Dry weight genset | kg | 13300 | 14900 | 13300 | 14900 |
Bore / stroke | mm | 170/195 | 170/195 | 170/195 | 170/195 |
Displacement | dm3 | 70.8 | 70.8 | 70.8 | 70.8 |
Speed | min-1 | 1500 | 1500 | 1500 | 1500 |
Mean piston speed | m/s | 9.8 | 9.8 | 9.8 | 9.8 |
The values given in these tables are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.
Service Intervals
TCG 2020 V12, V16, V20, V12 K, V16 | First service (check valve clearance) | Cylinder head inspection | Major overhaul |
Natural gas, purified biogas, sewage gas, and landfill gas | 4000 oh | 32000 oh* | 64000 oh |
Unpurified biogas, sewage gas, and landfill gas | 2000 oh | 16000 oh* | 64000 oh |
Visit our other generator sets that are available
Overview
- Category : Gas
- Item Number : H2326
- Offer Type : For Sale
- Quantity : 29
- Electrical Output : 1400KW
- Type of Equipment : Reciprocating
- Manufacture : MWM
- Model : TCG2020V16
- RPM : 1800
- Application : Industrial
- Rating : Continuous
- Fuel Type : Natural Gas
- Condition : Used
- Alternator : Stamford
- Frequency : 60 HZ
- Voltage : 480
- Phase : 3
- Mounted Type : Containerized Sound Attenuated
- Enclosure Certification : CE
- Electrical Equipment : Control Panel, Circuit Breaker, Synchronization Panel, Automatic Transfer Switch
- Installed/uninstalled : Installed
- Operational on Inspection : Yes
Features:
- TCG 2020 V16K (K Series is Optimized for robustness and low CAPEX
- MWM Power Modules
- Sound Attenuated Enclosures
- Runs on all gas types: natural gas, biogas, landfill gas, sewage gas, mine gas, etc.
- Low operating costs